Flame Safeguard
Primary Control
The RA890F Protectorelay™ Primary Control
is a nonprogramming, amplifying relay that pro-
vides solid state electronic flame safeguard pro-
tection for industrial and commercial gas, oil, or
combination gas-oil burners.
Employs rectification principle of electronic flame
detection using a flame rod, rectifying photocell, or
C7012A,C Ultraviolet Flame Detector.
Clipping pilot link jumper wire permits use with
standing pilots.
Can directly replace RA890E and mount on same
Q270A Subbase.
Solid state circuitry eliminates vacuum tube replace-
ment and increases resistance to vibration. Power
application not required during Off cycle; no tube to
warm up before starting.
Push-to-reset safety switch in dust-resistant enclosure.
Built-in protection against ignition crossover in flame
rod systems.
Does not start if flame-simulating failure occurs in
flame detector circuit.
Automatic safety shutdown if flame fails on start, or
if flame not re-established after flame failure.
Flame signal current is directly measurable at test
jack.
Line or 24 volt, automatic or manual controller can be
used. (Manual controller must open circuit on either
power or flame failure.)
Captive mounting screws allow easy mounting and
removal. Thermoplastic mounting base.
Optional alarm circuit indicates safety shutdown.
S.Y. • Rev. 11-94 • ©Honeywell Inc. 1994
60-2034-7
CONTENTS
Specifications ................................................. 2
Ordering Information ..................................... 2
Installation ..................................................... 4
Operation ....................................................... 7
Checkout......................................................... 8
Service .......................................................... 10
Troubleshooting and Maintenance ..............10
Vedere la pagina 0
1 2 3 4 5 6 ... 11 12

Sommario

Pagina 1

1 60-2034—7RA890FFlame SafeguardPrimary ControlThe RA890F Protectorelay™ Primary Controlis a nonprogramming, amplifying relay that pro-vides solid sta

Pagina 2 - Ordering Information

60-2034—7 10RA890FSERVICE • TROUBLESHOOTINGServiceGENERAL SERVICE1. Only qualified personnel should attempt to serviceheating equipment or controls.2.

Pagina 3 - 30 sec safety switch +10 -12

11 60-2034—7RA890FTROUBLESHOOTINGterminal 6 with the controller calling for heat. If there ispower at terminal 6 and a line voltage controller is used

Pagina 4 - Installation

60-2034—7 12Home and Building Control Home and Building Control Helping You Control Your WorldHoneywell Inc. Honeywell Limited—Honeywell Limitée1985 D

Pagina 5 - Fig. 2—Flame detector wiring

60-2034—7 2RA890FSPECIFICATIONS • ORDERING INFORMATIONSpecif icationsTRADELINE® MODELSTRADELINE® models of this device are available. Theyare select

Pagina 6 - INSTALLATION

3 60-2034—7RA890FSPECIFICATIONSNOTE: Allowable inrush can be up to ten times the pilotduty rating.EXAMPLE: Pilot duty rating = 25 VA.At 120V, running

Pagina 7 - Operation

60-2034—7 4RA890FINSTALLATIONInstallationWHEN INSTALLING THIS PRODUCT…1. Read these instructions carefully. Failure to fol-low them could damage the p

Pagina 8 - Checkout

5 60-2034—7RA890FINSTALLATIONIMPORTANT: Do not run high voltage ignition transformerwires in the same conduit with the flame detectorwiring.IMPORTANT:

Pagina 9

60-2034—7 6RA890FINSTALLATIONFig. 4—Oil system with interrupted ignition.M875312345POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS R

Pagina 10 - Troubleshooting

7 60-2034—7RA890FINSTALLATION • OPERATIONMOUNT RA890FDisconnect power supply.Remove relay cover (see Fig. 6) and position the RA890Fover the Q270A Sub

Pagina 11

60-2034—7 8RA890FCHECKOUTCheckoutIF A STEADY READING OF AT LEAST MINIMUMSTRENGTH CANNOT BE OBTAINED, ONE OR MOREOF THE FOLLOWING CONDITIONS CAN EXIST:

Pagina 12 - QUALITY IS KEY

9 60-2034—7RA890FCHECKOUTPILOT TURNDOWN TESTCAUTIONThe pilot turndown test should be performed onlyby qualified personnel and the instructions shouldb