GasPoint 4-20mA Fixed Gas Monitor Gas Transmitter Installation and Operating Instructions s

Pagina 2

GasPoint Page 3 Installation — System Design Specifications Page 6 System Design Specifications: Supply Voltage: 12 to 32 volts Power Cons

Pagina 3 - List of Tables:

GasPoint Page 3 Installation—Cable Installation Page 5 4-20 mA Loop Installation Cable Routing: Separate cables are required for each GasPoint.

Pagina 4 - Contacting BW Technologies

Figure 3: System Wiring Diagram (Exception GasPoints equipped with Communication Modules) Installation — System Wiring Page 8 LEGEND NC - Normally

Pagina 5

Page 3 Installation — Remote Sensor Separation Kit Page 9 Mounting the Sensor Separation Kit Enclosure 1. The Separation Kit is equipped with predril

Pagina 6

Page 3 Installation — Select Field Settings Page 10 Factory Settings: The GasPoint is calibrated and tested before shipping. Prior to shipping they a

Pagina 7 - Introduction

Dip Switches Table 4: The dipswitches are located on the upper control board. To access the dipswitch banks

Pagina 8 - Sensor Location

Connecting the Controller and Power Supply Ensure the GasPoint transmitter is complete with its external cover in place before applying power. Follow

Pagina 9 - Installation — Enclosure

Page 3 Page 9 Changing Setpoints Changing the Alarm Setpoints and Calibration Gas Setpoints The Setpoint Mode allows the user to change the calibratio

Pagina 10 - Cable Installation

Normal Operation The GasPoint provides continuous monitoring for the target gas. In the event of power failure, the GasPoint will automatically reset

Pagina 11

Gas Alarm Conditions and Advice If the current gas concentration meets or exceeds either alarm setpoint, the GasPoint gas alarm functions will activat

Pagina 13

GasPoint Sensor Advice The GasPoint sensor communicates constantly with the GasPoint transmitter, providing gas level concentrations and sensor status

Pagina 14 - Page 10

Page 17 Fault Alarm Conditions and Advice In the event of a fault condition, the fault alarm will trigger activating any connected field interface. Ga

Pagina 15 - Page 11

Calibration Page 18 Calibration Guidelines When calibrating the GasPoint, adhere to the following guidelines. Calibration accuracy is never better t

Pagina 16 - Power-Up

Calibration Page 19 Automatic Calibration Routine Calibration can be run at any time during normal operation except the self-test period (from 10 minu

Pagina 18 - Normal Operation

MAINTENANCE SERVICE Page 21

Pagina 19 - Gas Alarms Advice

To keep the GasPoint in good operating condition, perform the following basic maintenance as required: Calibrate, test, and inspect the GasPoint at

Pagina 20 - GasPoint Sensor Advice

SERVICE Page 23 Disassembling: Observe all safety and electrical codes and regulations before removing front cover. Unscrew the

Pagina 22 - Calibration Guidelines

APPENDIX A Sensor Information

Pagina 23

Table of Contents: Description

Pagina 24

Sensor Specifications Page 26 Sensors: Toxic and Oxygen: Electrochemical Combustible: Catalytic or Infrared (IR) Position Sensitivity: None Operat

Pagina 25 - SERVICE

Page 27 A P P E N D I X A Combustible Sensor Notes: Relative Sensitivity of Combustible Gases/Vapors Recommend: For the most accurate measurements

Pagina 26 - Maintenance

Specifications: MONITOR: 3-wire, 4-20 mA gas transmitter with advanced micro-controller based circuitry Power Input: 12 to 32 vo

Pagina 27 - Other Component Replacement

BW Technologies Limited Warranty BW Technologies warrants this product to be free from defects in material and workmanship under normal use and servi

Pagina 28

Notes: Page 30

Pagina 30 - Sensor Specifications

E-mail: [email protected] Visit our Web Site: www.gasmonitors.com D1374/3 t

Pagina 31 - Combustible Gases/Vapors

Safety Information — Read First IMPORTANT Users of the GasPoint require a full understanding of the operating and maintenance instructions. Use the m

Pagina 32 - Specifications:

Installation and Operating Instructions Manufacturer’s Notes and Warnings 1. Read the Safety Warnings and Cautions at the beginning

Pagina 33 - ORDER NUMBERS

Introduction Introduction The GasPoint provides continuous monitoring of the atmosphere for hazardous gases in the workplace and is virtually

Pagina 34 - Page 30

Elements Drawings 1a, 1b, 1c 1a GasPoint Monitor 1b Control Bay

Pagina 35

Sensor Location Several factors should be considered when selecting locations to install sensors. The following general suggestions should be consider

Pagina 36 - E-mail: [email protected]

GasPoint Mounting the Enclosure Modular design simplifies installation of the GasPoint. The transmitter main board is mounted to the inner control doo